Gas Generator G3516H

G3516H Generator Set

Get a Quote
Maximum Continuous Rating 2027 / 2007 ekW @ 1.0pf
Fuel Type Natural Gas
Maximum Electrical Efficiency 45.30%
Frequency 50 / 60 Hz
RPM 1500 / 1800 rpm
Engine Model G3516H
Displacement 4765 in³
Aspiration TA
Bore 6.7 in
Stroke 8.5 in
Compression Ratio 12.1
Fuel System Natural Gas
Length 291 in
Width 84 in
Height 95 in
Dry Weight - Genset 40384 lb
Control Panels
  • EMCP4.3
Air Inlet
  • Package Mounted Air Cleaner with service indicator
  • Two-element single-stage air cleaner with enclosure and service indicator
Cooling
  • Jacket water and SCAC driven thermostats
  • ANSI Class 150/DN custom flange connections for JW inlet and outlet
  • Engine driven water pumps for jacket water and after cooler
  • 2nd stage SCAC-Cat Flange
Exhaust
  • Center section cooled turbocharger with Cat flanged outlet
  • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
  • Dry exhaust manifolds, insulated and shielded
  • Cat-flanged face outlet on turbocharger
Fuel System
  • Throttle plate, 24V DC actuator, controlled by GECM
  • Electronic fuel metering valve
  • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
Ignition System
  • Electronic Ignition System (controlled by ADEM A4)
  • Individual Cylinder Detonation Sensitive Timing (DST)
Generator
  • Permanent Magnet Excitiation
  • Anti-condensation space heater
  • Winding temperature detectors
  • SR5
  • Reactive Droop
  • Caterpillar's Digital Voltage Regulator (CDVR) with 3-phase sensing and KVAR/PF control
General
  • Crankshaft vibration damper and guard
  • Paint - Caterpillar Yellow except rails and radiators gloss black
  • RH Service
  • Parts book
  • Operation and maintenance manuals
Governing System
  • ADEM A4 4-20mA (0-5V) Speed Input
Starting/Charging
  • 24V starting motors
Air Inlet
  • Mounting brackets and piping
  • Air cleaner with precleaner
  • Heavy Duty air cleaner with precleaner
Circuit Breakers
  • No UV trip or package mounted CB Wiring
  • Frame Mounting
  • MP-Frame 3 Pole Bottom Cable Entry or MP- Frame 6 Pole Bottom Cable Entry
  • 4000A, 3-Pole IEC Rated
  • 2500/3000/3200A or 4000/5000A Neutral Current Transformer Automatic Selection
  • Lower & Upper Covers, Extension Box Roof Cover
  • Busbar Mounting
  • 4000A, 3-Pole UL Rated
Control Panels
  • Remote monitoring software
  • Discrete I/O Module, 12 Digital Inputs, 8 'Form C' Relay
  • Remote RS485, 32-light Annunciator
  • Cat Connect: Ehternet, Satellite, Cell Telematics
  • Cross-Current Compensation Current Transformer-- 8.7/15 kV Classes
  • RTD Module
  • Local/Remote PC Monitorring
  • 16 Point/32 Light Annunciator with NFPA99-110/CSA282 Configuration
  • Remote Monitoring & Control
  • Synchronizing module
  • Local alarm module
Cooling
  • Jacket water coolant heater
  • Inlet/Outlet connections
Exhaust
  • Flange
  • Muffler and spark-arresting muffler with ANSI companion flanges
  • Elbow
Generator
  • Manual voltage control
  • Generator air filter
  • Low voltage extension box
  • Medium and high voltage generators and attachment
  • Cable access box
  • Bearing temperature detectors
Starting/Charging
  • 24V Battery Charger
  • 60A, 24V charging alternator (requires engine driven pumps)
General
  • US AID emblem
  • Special paint order
  • Battery diconnect switch
  • Digital diagnostic tool
  • Tool set
  • Battery with cables and rack (shipped loose)