G3412 Gas Generator Set

Get a Quote
Maximum Standby Rating 500 ekW @0.8pf
Fuel Type Natural Gas
Emissions/Fuel Strategy U.S. EPA Certified for Emergency Only Stationary Genset
Frequency 60 Hz
RPM 1800 rpm
Engine Model G3412
Displacement 1649 in³
Aspiration NA
Bore 5.4 in
Stroke 6 in
Length 165 in
Width 85.25 in
Height 86 in
Dry Weight - Genset 14700 lb
Air Inlet
  • Two-element single-stage air cleaner with enclosure and service indicator
  • Dual air cleaners, 1 per side, with service indicator
Control Panel
  • EMCP 4.3
Cooling
  • Package mounted radiator
  • LH or RG connections when radiator is not selected
  • Engine driven pumps for jacket water and separate circuit aftercooler
  • Jacket water and SCAC thermostats
Fuel
  • Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
  • Gas Train: NFPA37 and CSA B149.3
Exhaust
  • Dry exhaust manifolds, insulated and shielded
Fuel System
  • Engine-installed electronic control valve
  • Gas pressure regulator
  • 24V DC energized-to-run (ETR) gas shutoff valve
General
  • Paint- Caterpillar Yellow with gloss black rails and radiators
  • Operation and maintenance manuals
  • RH Service
  • Parts book
  • Crankshaft vibration damper and guard
Lubrication
  • Cartridge style oil filter
  • Gear type lube oil pump
Generator
  • Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
  • Anti-condensation space heater
  • Permanent Magnet Excitiation
  • Winding temperature detectors
Governing System
  • ADEM A4
Ignition System
  • Electronic Ignition System (controlled by ADEM A4)
  • Individual Cylinder Detonation Sensitive Timing (DST)
Starting/Charging
  • Electric Starter
  • 24V DC starting motors
Air Inlet
  • Air cleaner with precleaner
Circuit Breakers
  • S LSI
  • Frame mounting
  • Right, left, rear mounted
Control Panel
  • Local alarm module
  • Local PC monitoring
  • Remote PC monitoring
  • Remote annunciator
Cooling
  • Inlet/Outlet connections
  • Coolant level drain line with valves, fan with guard
Exhaust
  • Flexible fittings
  • 15, 25 dBA Attenuation
General
  • Digital diagnostic tool
  • Tool set
  • US AID emblem
Generator
  • Cable access box
  • Bearing temperature detectors
Starting/Charging
  • Battery with cables and rack (shipped loose)
  • 10A, 24VDC battery charger
  • Jacket water heater