D175 GC Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Get a Quote
Minimum Rating 175 ekW
Maximum Rating 175 ekW
Emissions/Fuel Strategy U.S. EPA Cert., Tier 3
Voltage 208 to 600 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby
Engine Model C7.1 I-6, 4-Cycle Diesel
Bore 4.1 in
Stroke 5.31 in
Displacement 427.8 in³
Compression Ratio 16.7:1
Aspiration Turbocharged, Air to Air Aftercooled
Fuel System Electronic, Common Rail
Governor Type ADEM™A4
Length - Maximum 103.7 in
Width - Maximum 51.2 in
Height - Maximum 58.7 in
Dry Weight - Genset (maximum) 3741 lb
Air Inlet System
  • Air Cleaner; light duty with disposable element
Control Panels
  • GCCP 1.2 control panel
Cooling System
  • Coolant drain line with valves
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
  • Radiator and cooling fan with guards
Generator and Generator Attachments
  • Tower panel, IP22, bottom cable entry
  • IP23 protection
  • 12 Leads
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
  • Segregated low voltage (AC/DC) wiring panel
  • Voltage regulator (single phase sensing)
Exhaust System
  • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use; shipped loose
Fuel System
  • Base, formed steel with single wall integral 24-hour fuel tank
  • Standard open set fuel tank / base supplied
Lube System
  • Lubricating oil
  • Oil drain line with valve
Mounting System
  • Termination points for coolant and lube oil drain lines
  • Includes lifting provision and drag points
  • Captive linear vibration isolators between base and engine-generator
Starting / Charging System
  • 24V Battery with rack and cables
Governing System
  • Mechanical and electrical governing system - model dependent
General
  • Engine and alternator pre-paint, Caterpillar Yellow
Alternator System
  • Permanent magnet
  • Quatrature droop king
  • Alternator removal
  • 3 Phase sensing
  • R frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
  • Anti-condensation heater
  • Optional LC frame alternator with coastal insulation protection
Circuit Breakers
  • Padlockable breaker device
  • 4 Pole 250A, 400A and 630A Circuit Breakers
Control Panel Options
  • Earth fault (2 wire only)
  • Speed adjust contacts
  • Panel mounted audible alarm
  • Volt free contacts
  • Earth leakage (2 wire only)
  • Overload shutdown via breaker
  • Control panel heater
  • Speed adjust potentiometer
  • Battery charger
  • Emergency stop with key
Control System
  • Static battery charger
  • Volt free contacts for common alarm
  • Volt free contacts for generator set running
  • GCCP 1.2
Cooling System
  • Low coolant temperature
  • Coolant heater
  • Low coolant level shutdown
Enclosures
  • Sound attenuated level 2 enclosure
Mounting Options
  • Electronic governor
  • Silencer installation kit
  • Industrial silencer removal
  • Battery removal
  • Residential silencer
Fuel Systems
  • Low fuel level alarm
  • Compact skidbase for open sets
  • DEFRA bunded fuel tank
  • Open set narrow tankbase
  • Low fuel level shutdown
  • Skidbase for CALG enclosure sets
  • High fuel level alarm
Test Reports
  • PGS test report @ 1.0 power factor
  • PGS test report @ 0.8 power factor
General
  • Stone guards / radiator trans flange
Global Certifications
  • Certification for CIS
Power Termination
  • Circuit breaker, IEC, 4 pole
Accessories / Miscellaneous
  • Packing case - compact set
  • Packing case - canopied set