Caterpillar electric power stands for reliable energy supply. Especially during the energy system transformation, Cat generator sets close the energy gap caused by renewable energy source such as wind and photo voltaic. Short ramp up time, low operating costs and rapid maintenance times ensures a high availability according to the need of our customers. Combined heat /cool and power solutions allow our customers to maximize the efficiency and earnings paired with low emissions. Wherever power is needed around the globe, Caterpillar is able to support you with the best products and services to maximize your profit.
Minimum Rating | 10580 kWe |
Maximum Rating | 14110 kWe |
Emissions/Fuel Strategy | (WB) Cert stage 1 and 2 |
Voltage | 3000 to 13800 Volts |
Frequency At Speed | 50 Hz @ 500 / 60 Hz @ 514 |
Duty Cycle | Prime, Continuous |
Ready To Accept Loads (Preheated/Vented) | 40 s |
Normal Ramp Up To 100% Load | 80 s |
Emergency Ramp Up 10% To 100% Load | 25 s |
Genset Efficiency Up To | 48.50% |
Engine Model | CM46DF V-Type, 4-stroke-engine |
Bore | 18.11 in |
Stroke | 24.02 in |
Aspiration | Turbocharged-aftercooled |
Engine Rating Range | 10800 - 14400 kW |
Configuration | 12,16 cylinder |
Fuel Type | Gas / diesel oil / heavy fuel oil (HFO) / crude oil |
Swept Volume | 6186 in³ |
Mean Effective Pressure Up To | 309 psi |
Specific Fuel Oil Consumption (WB I) Up To | 0.406 Ib/kWh |
Specific Fuel Oil Consumption (WB II) Up To | 0.406 Ib/kWh |
Specific Lube Oil Consumption | 0.001 Ib/kWh |
Length - Minimum | 562 in |
Length - Maximum | 652 in |
Width - Minimum | 153 in |
Width - Maximum | 159 in |
Height - Minimum | 183 in |
Height - Maximum | 188 in |
Dry Weight - Genset (minimum) | 500449 lb |
Dry Weight - Genset (maximum) | 630521 lb |