Caterpillar electric power stands for reliable energy supply. Especially during the energy system transformation, Cat generator sets close the energy gap caused by renewable energy source such as wind and photo voltaic. Short ramp up time, low operating costs and rapid maintenance times ensures a high availability according to the need of our customers. Combined heat /cool and power solutions allow our customers to maximize the efficiency and earnings paired with low emissions. Wherever power is needed around the globe, Caterpillar is able to support you with the best products and services to maximize your profit.
"*" indicates required fields
Minimum Rating | 985 kWe |
Maximum Rating | 1650 kWe |
Emissions/Fuel Strategy | (WB) Stage 1 and 2 |
Voltage | 3000 to 13800 Volts |
Frequency At Speed | 50 Hz @ 1000 / 60 Hz @ 900 |
Duty Cycle | Prime, Continuous |
Ready To Accept Loads (Preheated/Vented) | 40 s |
Normal Ramp Up To 100% Load | 75 s |
Emergency Ramp Up 10% To 100% Load | 25 s |
Genset Efficiency Up To | 43.10% |
Engine Model | CM20C, 4-stroke-engine |
Bore | 7.87 in |
Stroke | 11.81 in |
Aspiration | Turbocharged-aftercooled |
Engine Rating Range | 1020 - 1710 kW |
Configuration | 6,8,9 cylinder |
Fuel Type | Diesel oil / heavy fuel oil (HFO) / crude oil |
Swept Volume | 575 in³ |
Mean Effective Pressure Up To | 351 psi |
Specific Fuel Oil Consumption (WB I) Up To | 0.417 Ib/kWh |
Specific Fuel Oil Consumption (WB II) Up To | 0.417 Ib/kWh |
Specific Lube Oil Consumption | 0.001 Ib/kWh |
Length - Minimum | 239 in |
Length - Maximum | 281 in |
Width - Minimum | 66 in |
Width - Maximum | 71 in |
Height - Minimum | 112 in |
Height - Maximum | 119 in |
Dry Weight - Genset (minimum) | 41447 lb |
Dry Weight - Genset (maximum) | 66139 lb |