C18 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Get a Quote
Minimum Rating 500 ekW
Maximum Rating 600 ekW
Emissions/Fuel Strategy Low Fuel Consumption
Voltage 220 to 380 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime
Engine Model C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 5.71 in
Stroke 7.2 in
Displacement 1106.4 in³
Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Fuel System Electronic unit injection
Governor Type Adem™A4
Length - Maximum 218.5 in
Width - Maximum 80.9 in
Height - Maximum 107.8 in
Air Inlet
  • Air Cleaner
Cooling
  • Package mounted radiator
Exhaust
  • Exhaust flange outlet
Fuel
  • Fuel priming pump
  • Secondary fuel filter
  • Primary fuel filter with integral water separator
Generator
  • IP23 Protection
  • Matched to the performance and output characteristics of Cat engines
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
Power Termination
  • Bus Bar
Control Panel
  • EMCP 4.2
Mounting
  • Rubber vibration isolators
Starting/Charging
  • 24 volt starting motor
  • Batteries
General
  • Paint - Caterpillar Yellow except rails and radiators gloss black
Exhaust
  • Industrial, Residential, Critical Mufflers
Generator
  • Anti-condensation heater
  • Oversize and premium generators
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
Control Panels
  • Remote monitoring software
  • Local & remote annunciator modules
  • Digital I/O module
  • EMCP 4.4
  • Load share module
Starting/Charging
  • Oversize batteries
  • Battery chargers
  • Heavy-duty starting system
  • Jacket water heater
  • Charging alternator
General
  • Narrow, Wide or Skid Base
  • CSA Certification
  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • Enclosures: sound attenuated, weather protective
  • Single or dual wall integral fuel tanks
  • Integral & sub-base UL listed dual wall fuel tanks
  • Automatic transfer switches (ATS)
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • The following options are based on regional and product configuration:
  • Single or dual wall sub-base fuel tanks
  • EEC Declaration of Conformity
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007