XQP150

Generator

Rating
150 kVA Prime
Frequency
50/60 Hz
Voltage
127 - 480 V
Prime Power
9.9gal/hr
IPP Rated 60Hz
73.1 dB(A)
Rating Prime
150 kVA

Engine

Engine
C7.1 Diesel Engine or C7.1 ACERT Diesel Engine
Fuel
Diesel

Dimensions

Width
44.1in
Height
87.6in
Length
138.6in
Weight
5615lb

Fuel Consumption EU Stage IIIA

100% Load 60Hz
11.2gal/hr
75% Load 50Hz
7.8gal/hr
75% Load 60Hz
9.2gal/hr
50% Load 50Hz
5.4gal/hr
50% Load 60Hz
6.3gal/hr
100% Load 50Hz
9.9gal/hr
100% Load 60Hz
11.2gal/hr
75% Load 50Hz
7.8gal/hr
75% Load 60Hz
9.2gal/hr
50% Load 50Hz
5.4gal/hr
50% Load 60Hz
6.3gal/hr

Fuel consumption Best Fuel Efficiency

100% Load 50Hz
8.8gal/hr
100% Load 60Hz
10.5gal/hr
75% Load 50Hz
6.5gal/hr
75% Load 60Hz
7.7gal/hr
50% Load 50Hz
4.3gal/hr
50% Load 60Hz
5gal/hr
100% Load 50Hz
8.8gal/hr
100% Load 60Hz
10.5gal/hr
75% Load 50Hz
6.5gal/hr
75% Load 60Hz
7.7gal/hr
50% Load 50Hz
4.3gal/hr
50% Load 60Hz
5gal/hr

Noise rating (with enclosure) EU Stage IIIA

Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
76.4 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
73.1 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
76.4 dB(A)

Noise rating (with enclosure) Best Fuel Efficiency

Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
74.7 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
78.3 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz)
74.7 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz)
78.3 dB(A)

Standard Equipment

  • Cat C7.1 Diesel Engine
    • Turbo charged.
  • Generator
    • LC3114J frame.
  • Air Filter
    • Cyclonic/paper with dust cup and service indicator.
  • Cat Connect Remote Monitoring
    • Provides package monitoring and management.
  • Cooling System
    • Package mounted radiator with vertical air discharge. Filled from factory.
  • Charging / Starting System
    • 12V heavy duty starting motor and charging alternator c/w battery isolator.
  • Fuel System
    • 24hr dual wall fuel tank with 3 way directional valve for external supply.
  • Control Panel
    • Digital EMCP4.2B set mounted controller.
  • Distribution
    • Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off.
  • Structure
    • Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. Base frame is wider than enclosure to protect generator set during transportation.
  • Enclosure
    • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance.
  • Exhaust
    • Integrated spark arresting silencer.
  • Lube Oil
    • On engine primary and secondary oil filters. Filled from factory.
  • General
    • Factory tested and inspected.