CM25C Generator Set

Generator Set Specifications

Genset Rating Range
1735 - 2600 kWe
Emission Level Up To
World bank emission certification (Stage 2)
Voltage
3000 to 13800 Volts
Frequency At Speed
50 Hz @ 750 / 60 Hz @ 720
Aspiration
Turbocharged-aftercooled
Bore
10.04in
Stroke
15.75in
Emergency Ramp Up 10% To 100% Load
25 s
Genset Efficiency Up To
44.20%
Normal Ramp Up To 100% Load
75 s
Ready To Accept Loads (Preheated/Vented)
40 s
Minimum Rating
1735 kWe
Maximum Rating
2600 kWe
Emissions/Fuel Strategy
(WB) Cert stage 1 and 2
Duty Cycle
Prime, Continuous

Engine Specifications

Engine Rating Range
1800 - 2700 kW
Engine Type
4-stroke-engine
Configuration
6,8,9 cylinder
Fuel Type
Diesel oil / heavy fuel oil (HFO) / crude oil
Specific Fuel Oil Consumption (WB I) Up To
0.406Ib/kWh
Specific Fuel Oil Consumption (WB II) Up To
0.408Ib/kWh
Specific Lube Oil Consumption
0.001Ib/kWh
Mean Effective Pressure Up To
355psi
Swept Volume
1247in³
Engine Model
CM25C, 4-stroke-engine
Bore
10.04in
Stroke
15.75in
Aspiration
Turbocharged-aftercooled

Generator Set Dimensions

Length - Minimum
318in
Length - Maximum
375in
Width - Maximum
100in
Width - Minimum
98in
Height - Minimum
154in
Height - Maximum
156in
Dry Weight - Genset (minimum)
94799lb
Dry Weight - Genset (maximum)
123459lb

Standard Equipment

  • Fuel System
    • Gas valve unit (GVU) (only dual fuel (DF) and gas)
    • Engine ventilation module (only dual fuel (DF) and gas)
    • Circulation module
    • Separator module
    • Pre-pressure module
    • Ignition fuel oil module (only dual fuel (DF))
  • Lubricating Oil System
    • Combined module: cooling water system and lube oil system
    • Lube oil separator module
    • Piping interface module
  • Cooling Water System
    • Cooling water system with radiators
    • Piping interface module
    • Combined module: see lube oil system
  • Starting System
    • Starting air receiver module
    • Starting air compressor module
  • Combustion Air System
    • Air filter - pulse
    • Air filter - oil bath
    • Air filter - pocket
  • Exhaust System
    • Oxidation catalytic (Oxicat) converter system
    • Exhaust gas ventilation module (only dual fuel (DF) and gas)
    • Exhaust gas silencer
    • Selective catalytic reduction (SCR) system
  • Control & Monitoring System
    • Gas leak detection per cylinder (only dual fuel (DF) and gas)
    • Local data panel (LDP) / generator control panel (GCP)
    • Engine monitoring package
    • Local control panel (LCP)
    • Motor control center module (MCC)
  • Mounting System
    • Elastic mounting - genset/engine