Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Engine Specifications

Bore
6.69in
Displacement (HD)
4764.73in3
Stroke (HD)
8.46in
Aspiration
TA
Fuel System
Electronic unit injection
Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Displacement - Std
4210.64in³
Stroke - Standard
7.48in
Compression Ratio
14.0:1
Governor Type
Adem™3
Aspiration
TA
Fuel System
Electronic unit injection
Bore
6.69in
Displacement - HD
4764.73in³
Stroke - HD
Stroke
7.48in
Displacement
69in

Generator Set Specifications

Minimum Rating
1750 kVA
Maximum Rating
2250 kVA
Voltage
380 to 11000 Volts
Frequency
50 Hz
Speed
1500 rpm
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Generator Set Dimensions

Height - Maximum
93.2in
Length - Maximum
6377in
Width - Maximum
90in
Length - Minimum
233.4in
Dry Weight - Genset (minimum)
31900lb
Dry Weight - Genset (maximum)
40320lb

Standard Equipment

  • Air Inlet System
    • Air Cleaner; single element canister type
  • Air Inlet
    • Air Cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Fuel priming pump
    • Secondary fuel filter
    • Primary fuel filter with integral water separator
  • Generator
    • IP23 Protection
    • Matched to the performance and output characteristics of Cat engines
  • Power Termination
    • Bus Bar
  • Control Panels
    • Programmable protective relaying functions:
    • Low coolant temperature
    • Reverse power (kW) (32)
    • Low coolant level
    • Environmental sealed front face
    • KVAR/PF modes
    • 6 Customer programmable digital inputs
    • Reverse reactive power (kVAr) (32RV)
    • Reactive droop capability
    • Over / under voltage (2 7/ 59)
    • 0 True RMS AC metering, 3-phase, +/-2% accuracy
    • EMCP 4.2B
    • Operating hours
    • Power Factor (per phase & average)
    • Coolant temperature
    • Digital indication for:
    • kVA (per phase, average & percent)
    • 3-phase voltage sensing
    • 4 Programmable relay outputs (Form A)
    • 4 Programmable relay outputs (Form A)
    • kW (per phase, average & percent)
    • Failure to start (overcrank)
    • Alarm acknowledge
    • Low oil pressure
    • Oil pressure (psi, kPa or bar)
    • Accessory module data link
    • Generator set packages include Caterpillar' s Voltage Regulator
    • 24 Volt DC operation
    • Auto/start/stop control
    • Min / max exciter
    • Amps (per phase & average)
    • Controls:
    • Speed adjust
    • Limiter and exciter diode monitor
    • Generator mounted - rear facing
    • Overspeed - Emergency stop
    • RPM - DC volts
    • Cat Connect
    • Warning / shutdown with common LED indication of shutdowns for:
    • High coolant temperature
    • DC volts
    • PLC functionality
    • Serial annunciator module data link
    • kW-hr (total) - kVAr-hr (total)
    • 1 Programmable digital outputs
    • Customizable screens
    • Frequency (Hz)
    • IVR includes:
    • Text alarm/event descriptions
    • 1 Programmable relay outputs (Form C
    • Over / under frequency (81 o/u)
    • Load histogram feature
    • Communications:
    • 3 Analog inputs
    • RFI suppression
    • Overcurrent (50 / 51)
    • Emergency stop pushbutton
    • Engine cool-down timer
    • Volts (L-L & L-N)
    • Number of I/O varies on options selected:
    • Emergency stop - Failure to start (overcrank)
    • Engine cycle crank
    • Customer data link (Modbus RTU)
    • Lamp test
  • Control Panel
    • EMCP 4 Genset Controller
  • Cooling System
    • ATAAC - 3516E Package Radiators shipped installed
    • Certified standard PGS provided
  • Exhaust System
    • Flanged faced outlet(s)
    • Dry exhaust manifold
  • Fuel System
    • Fuel priming pump
    • Flexible fuel lines - shipped loose
    • Secondary fuel filters
    • Fuel cooler; not included with packages without radiator
  • General
    • Paint - Caterpillar Yellow except rails and radiators gloss black
    • Right hand servicing
    • SAE Standard rotation
    • Flywheel and flywheel housing - SAE No. 00
    • Caterpillar yellow with high gloss black rails and radiator
  • Generator And Attachments
    • Low Voltage:
    • 6 Leads
    • Internal excitation
    • Form wound
    • Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
    • Permanent magnet
    • Winding temperature detectors
    • Anti Condensation Space Heater
    • Permanent magnet
    • NEMA Class H insulation
    • Class H temperature rise at 40C ambient (125C prime / 150C standby)
    • Busbar connections, right side extension box, bottom cable entry
    • NEMA standard hole pattern
    • Winding temperature detectors
    • 3 Phase brushless, salient pole
    • Medium Voltage:
    • High Voltage:
    • Form wound - Permanent magnet
    • Random wound
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby
    • Busbar connections, top center mounted, top cable entry
    • NEMA standard hole pattern
    • Winding temperature detectors
  • Governing System
    • ADEM A3
  • Literature
    • English
  • Lubrication System
    • Gear type lube oil pump
    • Oil filter, filler and dipstick
    • Integral lube oil cool
    • Lubricating oil
    • Oil drain lines and valve
    • Fumes disposal
  • Mounting System
    • Anti-vibration mounts (shipped loose)
    • Rubber anti-vibration mounts (shipped loose)
    • Rails - engine / generator / radiator mounting
  • Starting System
    • 24 Volt electric starting motor
    • Battery disconnect switch
    • Battery and battery rack w/cables
    • 45 Amp charging alternator

Optional Equipment

  • Control System
    • EMCP 4.3, EMCP 4.4
  • Exhaust
    • Exhaust mufflers
  • Air Inlet System
    • Single element filter
    • Dual element air cleaner
  • Generator
    • Anti-condensation heater
    • Permanent magnet excitation (PMG)
    • Oversize and premium generators
    • Internal excitation (IE)
  • Cooling System
    • Optional installed radiators
    • Coolant
    • Standard ambient ATAAC radiators
    • Optional installed ATAAC radiators
    • Water level switch gauges
    • Standard ambient radiators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Crankcase System
    • Explosion relief valves
    • No explosion relief valves
    • Ventilation system
  • Control Panels
    • Load share module
    • Generator temperature monitoring & protection
    • Remote monitoring software
    • EMCP 4.2
    • EMCP 4.3
    • EMCP 4.4
    • Digital I/O module
  • Exhaust System
    • Y-Adapters
    • Flange and exhaust expanders
    • Flanges
    • Exhaust offset
    • Tier 4 clean emissions module
    • Tier 4 clean emission MOD Kits
    • Mufflers
    • Clean emission parts
    • Tier 4 dosing cabinet
    • Elbows
    • Flexible fittings
  • Fuel System
    • Primary Fuel Filter
    • Fuel Priming Pumps (Tier 4) - Manual or electric
  • General
    • US aid emblem
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
    • The following options are based on regional and product configuration:
    • EEC Declaration of Conformity
    • Integral & sub-base fuel tanks
    • CSA Certification
    • Automatic transfer switches (ATS)
    • Enclosures: sound attenuated, weather protective
    • EU Certificate of Conformance (CE)
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • Integral & sub-base UL listed dual wall fuel tanks
    • UL 2200 package
  • Starting/charging
    • Jacket water heater
    • Charging alternator
    • Battery chargers
    • Oversize batteries
    • Heavy-duty starting system
    • Air starting motor with control and silencer
  • Generators And Attachments
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
    • Thermostate for space heater
    • Space heater
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Generator conversion
    • Differntial current transformers (DCT) 8.7 kV and 15 kV classes
    • Alternator air cleaner
    • Differential current transformers (DCT)
  • Instrumentation
    • Pyrometer and thermocouples
  • Lubrication System
    • Oil level regulator
    • Prelube pumps
    • Lube oil in standard sump
  • Mounting System
    • IBC vibration isolators
    • Spring type vibration isolators
    • Puck style low efficiency isolators
  • Mounting
    • Spring-type vibration isolator
    • IBC isolators
    • Rubber anti-vibration mounts
  • Power Connections
    • Neutral ground connections
    • Center post busbar
    • Right side power connections
    • Ground cables between generator and terminal box
    • Rear power connections
    • 2700 Frame, four lead, four terminal
    • Left side power connections
    • Low voltage circuit breakers
  • Special Tests / Reports
    • PGS test report @ 0.8 power factor
    • Torsional vibration analysis reports
    • PGS test report @ 1.0 power factor
    • Fuel consumption test
    • generator test report
    • Standard engine test charge
    • OSHPD certification
    • Generator set fuel consumption test
    • Canadian Standards Association certification
    • IBC certification
  • Starting And Charging
    • Starter cover
    • 24 Volt battery set - Dry
    • Electric starting motors
    • Engine barring device
    • Air starting motors
    • Jacket water heaters
    • Air pressure regulator
    • 10, 20, 35 and 50 amp battery chargers
  • Extended Service Coverage
    • Platinum, Gold and Silver coverage