3516B Generator Set - Altorfer    

3516B Generator Set

3516B Generator Set

The 3516B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance that matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Engine Specifications

Bore
6.69in
Displacement (HD)
4764.73in3
Stroke (HD)
8.46in
Aspiration
TA
Fuel System
Electronic unit injection
Engine Model
3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Displacement - Std
4210.64in³
Stroke - Standard
7.48in
Compression Ratio
15.5:1
Governor Type
Adem™3
Exhaust Flange Size
203.2 mm (8.0 in)
Air Inlet
Single element canister style with service indicator
Aspiration
TA
Fuel System
Electronic unit injection
Bore
6.69in
Displacement - HD
4764.73in³
Stroke - HD
Air Inlet
Single element canister style with service indicator
Exhaust Flange Size
203.2 mm (8.0 in)
Stroke
8.46in
Displacement
4764.73in

Generator Set Specifications

Minimum Rating
2000 kVA
Maximum Rating
2500 kVA
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime, Continuous
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Generator Set Dimensions

Height - Maximum
98.2in
Length - Maximum
247.3in
Width - Maximum
90in
Dry Weight - Genset (maximum)
34250lb

Standard Equipment

  • Air Inlet System
    • Air Cleaner; single element canister type
  • Control Panels
    • 1 Programmable digital outputs
    • Digital indication for
    • Frequency (Hz)
    • 4 Programmable relay outputs (Form A)
    • High coolant temperature
    • Controls:
    • Low oil pressure
    • Customer data link (Modbus RTU)
    • Load histogram feature
    • PLC functionality
    • EMCP 4.2
    • Warning / shutdown with common LED indication of shutdowns for:
    • Lamp test
    • Number of I/O varies on options selected:
    • Accessory module data link
    • Engine cycle crank
    • Over / under frequency (81 o/u)
    • Customizable screens
    • Programmable protective relaying functions:
    • kVA (per phase, average & percent)
    • Emergency stop pushbutton
    • Reverse reactive power (kVAr) (32RV)
    • Generator set packages include Caterpillar' s Voltage Regulator. IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min/max exciter. Limiter and exciter diode monitor
    • 6 Customer programmable digital inputs
    • Alarm acknowledge
    • Generator mounted - rear facing
    • 0 True RMS AC metering, 3-phase, +/-2% accuracy
    • DC volts
    • Generator phase sequence
    • Text alarm/event descriptions
    • kW-hr (total)
    • Engine cool-down timer
    • Over / under voltage (27/59)
    • Cat connect
    • Overspeed
    • Serial annunciator module data link
    • kW (per phase, average & percent)
    • Amps (per phase & average)
    • 1 Programmable relay outputs (Form C)
    • Coolant temperature
    • Overcurrent (50/51)
    • Volts (L-L & L-N)
    • Auto/start/stop control
    • Power Factor (per phase & average)
    • Operating hours
    • Environmental sealed front face
    • kVAr (per phase, average & percent)
    • Low coolant level
    • 24 Volt DC operation
    • kVAr-hr (total)
    • Communications:
    • Speed adjust
    • Emergency stop
    • Reverse power (kW) (32)
    • 3 Analog inputs
    • Oil pressure (psi, kPa or bar)
    • Low coolant temperature
    • Failure to start (overcrank)
    • RPM
  • Cooling System
    • ATAAC - 3516E Package Radiators shipped installed
    • Certified standard PGS provided
  • Exhaust System
    • Flanged faced outlet(s)
    • Dry exhaust manifold
  • Fuel System
    • Fuel priming pump
    • Secondary fuel filters
    • Flexible fuel lines - shipped loose
    • Fuel cooler; not included with packages without radiator
  • General
    • Right hand servicing
    • SAE standard rotation
    • Caterpillar yellow with high gloss black rails and radiator
    • Flywheel and flywheel housing - SAE No. 00
  • Generator And Attachments
    • Low voltage:
    • Winding temperature detectors
    • Busbar connections, top center mounted, top cable entry
    • NEMA standard hole pattern
    • Permanent magnet
    • 3 Phase brushless, salient pole
    • Random wound
    • 6 Leads
    • Permanent magnet
    • High voltage:
    • Form wound
    • Winding temperature detectors
    • Form wound
    • Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
    • Winding temperature detectors
    • Medium voltage:
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Busbar connections, right side extension box, bottom cable entry
    • NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
    • NEMA standard hole pattern
    • Anti condensation Space heater
    • Internal Excitation
  • Governing System
    • ADEM A3
  • Literature
    • English
  • Lubrication System
    • Lubricating oil
    • Gear type lube oil pump
    • Fumes disposal
    • Integral lube oil cool
    • Oil drain lines and valve
    • Oil filter, filler and dipstick
  • Mounting System
    • Rubber anti-vibration mounts (shipped loose)
    • Anti-vibration mounts (shipped loose)
    • Rails - engine/generator/radiator mounting
  • Starting System
    • Battery and battery rack w/cables
    • 45 Amp charging alternator
    • 24 Volt electric starting motor
    • Battery disconnect switch

Optional Equipment

  • Control System
    • EMCP4.3, EMCP 4.4
    • Controller: [ ] EMCP 4.2 [ ] EMCP 4.3 [ ] EMCP 4.4
    • Local annunciator module: [ ] NFPA 110 [ ] Custom
  • Air Inlet System
    • Single element filter
    • Dual element air cleaner
  • Engine Options
    • Batteries: [ ] Standard (1400 CCA) [ ] Heavy Duty (2800 CCA)
    • Air Cleaner: [ ] Single element air cleaners [ ] Dual element air cleaners [ ] Heavy duty air cleaners
    • Starting Motors: [ ] Standard [ ] Heavy Duty
    • Battery Charger: [ ] 10A [ ] 20A [ ] 35A
    • Starting Aids: [ ] 220V 50 Hz Jacket Water Heater
    • Muffler: [ ] Industrial Grade
  • Cooling System
    • Coolant
    • Standard ambient ATAAC radiators
    • Optional installed ATAAC radiators
    • Water level switch gauges
    • Standard ambient radiators
    • Optional installed radiators
  • Crankcase System
    • Explosion relief valves
    • No explosion relief valves
    • Ventilation system
  • Alternators
    • Temperature Rise (over 40°C ambient): [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
  • Exhaust System
    • Y-Adapters
    • Flanges
    • Clean emission parts
    • Mufflers
    • Flange and exhaust expanders
    • Tier 4 clean emissions module
    • Tier 4 dosing cabinet
    • Flexible fittings
    • Elbows
    • Exhaust offset
    • Tier 4 clean emission MOD Kits
  • Power Termination
    • Power Termination: [ ] Bus Bar [ ] Circuit Breaker
    • Circuit Breaker rating: [ ] 2000A [ ] 2500A [ ] 3200A [ ] 4000A
    • Circuit breaker trip unit: [ ] LSI [ ] LSIG [ ] LSIG-P
  • Fuel System
    • Fuel Priming Pumps (Tier 4) - Manual or Electric
    • Primary Fuel Filter
  • Extended Service Contract (esc)
    • Extended Service Contract (ESC): [ ] 2 Year [ ] 3 Year [ ] 5 Year
  • General
    • Special paint (Colors other than Caterpillar yellow or high performance paints)
    • US aid emblem
  • Generators And Attachments
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
    • Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
    • Alternator air cleaner
    • Space heater
    • Thermostate for space heater
    • Differntial current transformers (DCT) 8.7 kV and 15 kV classes
    • Differential current transformers (DCT)
    • Generator conversion
  • Instrumentation
    • Pyrometer and Thermocouples
  • Lubrication System
    • Oil level regulator
    • Prelube pumps
    • Lube oil in standard sump
  • Mounting System
    • IBC vibration isolators
    • Puck style low efficiency isolators
    • Spring type vibration isolators
  • Power Connections
    • Neutral ground connections
    • Ground cables between generator and terminal box
    • 2700 Frame, four lead, four terminal
    • Left side power connections
    • Low voltage circuit breakers
    • Rear power connections
    • Center post busbar
    • Right side power connections
  • Special Tests / Reports
    • PGS test report @ 0.8 power factor
    • Generator set fuel consumption test
    • PGS test report @ 1.0 power factor
    • Standard engine test charge
    • OSHPD certification
    • Fuel consumption test
    • generator test report
    • Canadian Standards Association certification
    • IBC certification
    • Torsional vibration analysis reports
  • Starting And Charging
    • Air starting motors
    • Starter cover
    • 10, 20, 35 and 50 amp battery chargers
    • Air pressure regulator
    • Electric starting motors
    • 24 Volt battery set - Dry
    • Jacket water heaters
    • Engine barring device
  • Extended Service Coverage
    • Platinum, Gold and Silver coverage