XQ570

Generator

Rating
455 ekW (568 kVA) Prime
Frequency
60 Hz
Voltage
208 - 600 V

Engine

Engine
C18 ACERT™ Diesel

Dimensions

Width
96in
Height
102in
Length
282in

Standard Equipment

  • Air Inlet System
    • Heavy-duty air cleaner w/precleaner, two-stage cyclonic/paper with dust cup and service indicator.
  • Cat Cem
    • CEM comes with integrated CRS, DOC, DPF & SCR and is located in separate compartment.
  • Def System
    • 25 gal plastic DEF tank provides 24 hours runtime @ 75% + 10% rating similar to fuel system.
  • Fuel System
    • 700 gal (2650 L) double-wall fuel tank, UL142, ULC, and Transport Canada certified, 27-hour runtime @75% prime + 10% rating, internal fuel fill.
  • Generator
    • Three-phase, random wound, coastal insulation protection, 0.6667 pitch, permanent magnet excited, Class H insulation with Class F temperature rise.
  • Charging System
    • UL/CSA listed 120V, 20 amp battery charger, shock-mounted and enclosed in dust-proof housing.
  • Lube System
    • Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve.
  • Mounting System
    • Generator set soft mounted to the heavy duty, fabricated steel base frame.
  • Starting System
    • Single electric starting motor, 24V.
  • General
    • CSA approved
  • Containerized Module
    • 20' ISO standard cube container
  • Cooling
    • Standard cooling provides 43°C ambient capability (60 Hz) at prime +10% rating
  • Generator Set Controls And Protection
    • EMCP 4.4 generator set mounted controller
  • Quality
    • Factory testing of standard generator set and complete power module

Optional Equipment

  • Trailer
    • Full frame support Independent tandem axle trailer frame with tongue Electric actuated hydraulic brakes with rechargeable battery backup breakaway system. Overcenter mechanical parking brake Full length fenders Non-skid surface on steps Heavy duty safety chains and grab hooks Reinforced 4540 kg (10,000 lb) top wind drop jack.