C7.1 ACERT

C7.1 ACERT

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Download Product Documents

Generator Set Specifications

Minimum Rating
114 ekW
Maximum Rating
200 ekW
Voltage
208 to 480 Volts
Frequency
60 Hz
Speed
1800 RPM

Generator Set Configurations

Emissions/Fuel Strategy
U.S. EPA Certified for Stationary Emergency Use Only ( Tier 3 Nonroad Equivalent Emission Standards)

Engine Specifications

Engine Model
C7.1 I-6, 4-Cycle Diesel
Bore
4.13in
Displacement
427.8in³
Stroke
5.31in
Compression Ratio
16.5:1
Aspiration
Turbocharged, Air to Air Aftercooled
Governor Type
ADEM™A4
Fuel System
Common Rail

Standard Equipment

  • Packaged Generator Set
    • Dry replaceable paper element type with restriction indicator
    • Radiator and cooling fan complete with protective guards
    • Standard ambient temperatures up to 50°C (122°F)
    • Flexible fuel lines to base NPT connections
    • Class H insulation
    • Drip proof generator air intake (NEMA 2, IP23)
    • Class H temperature rise
    • Electrical design in accordance with with BS5000 Part 99, EN61000-6, IEC60034-1, NEMA MG-1.33
    • IP23 protection
    • Circuit breakers - 100% rated assembly, UL Listed
    • Power Center houses EMCP controller and power/control terminations
    • Segregated low voltage wiring termination panel
    • EMCP 4.2 Digital Control Panel
    • Vibration isolated NEMA 1 steel enclosure with lockable hinged door
    • DC and AC Wiring harnesses
    • Heavy-duty fabricated steel base with lifting points
    • Anti-vibration pads to ensure vibration isolation
    • Stub-up pipe ready for connection to silencer pipework
    • 12 volt starting motor
    • 24 volt, 45 amp charging alternator
    • Batteries with rack and cables
    • High gloss polyurethane paint, Caterpillar Yellow except rails and radiators gloss black
    • All electroplated hardware
    • Anticorrosive paint protection

Optional Equipment

  • Packaged Generator Set Options
    • Radiator stone guard
    • Radiator transition flange
    • Industrial, Residential, Critical Mufflers
    • Overhead silencer mounting kit
    • Sub-base dual wall UL listed 354 gallon fuel tank
    • Sub-base dual wall UL listed 690 gallon fuel tank
    • Emergency vent 12ft extension
    • 5 gallon spill containment
    • Generator upgrade 1 size
    • Permanent magnet excitation (PMG)
    • Internal excited (IE)
    • Anti-condensation space heaters
    • Auxiliary contacts
    • Shunt trips
    • Overload shutdown via breaker
    • NFPA110 upgrade
    • Lube oil heater
    • IBC Seismic certification per Applicable Building Codes: IBC2000, IBC2003, IBC2006, IBC 2009, IBC 2012, CBC 2007, CBC 2010
    • Battery charger - UL 10 amp
    • Battery disconnect switch
    • Coolant heater
    • CSA
    • Sound attenuated protective enclosure
    • High Ambient enclosure with integral lifting frame
    • Caterpillar tool set
    • Caterpillar White paint