C32 Generator Set

C32 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Download Product Documents

Generator Set Specifications

Minimum Rating
830 ekW (910 kVA)
Maximum Rating
1000 ekW (1250 kVA)
Voltage
220 to 4160
Frequency
50 or 60 Hz
Speed
1500 or 1800 RPM

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption, Low Emissions, EPA Certified for Stationary Emergency Application (Emits Equivalent U.S. EPA Tier 2 Nonroad Standards)

Engine Specifications

Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Displacement
1958.86in³
Stroke
6.38in
Compression Ratio
15.0:1
Aspiration
TA
Governor Type
Adem™A4
Fuel System
MEUI

Standard Equipment

  • Air Inlet
    • Air Cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Primary fuel filter with integral water separator
    • Secondary fuel filter
    • Fuel priming pump
  • Generator
    • Matched to the performance and output characteristics of Cat engines
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
    • IP23 Protection
  • Power Termination
    • Bus Bar
  • Control Panel
    • EMCP 4 Genset Controller
  • General
    • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment

  • Exhaust
    • Exhaust mufflers
  • Generator
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Anti-condensation heater
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • EMCP (4.2) (4.3) (4.4)
    • Generator temperature monitoring & protection
    • Load share module
    • Digital I/O module
    • Remote monitoring software
  • Mounting
    • Rubber anti-vibration mounts
    • Spring-type vibration isolator
    • IBC isolators
  • Starting/charging
    • Battery chargers
    • Oversize batteries
    • Jacket water heater
    • Heavy-duty starting system
    • Charging alternator
    • Air starting motor with control and silencer
  • General
    • The following options are based on regional and product configuration:
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • UL 2200 package
    • EU Certificate of Conformance (CE)
    • CSA Certification
    • EEC Declaration of Conformity
    • Enclosures: sound attenuated, weather protective
    • Automatic transfer switches (ATS)
    • Integral & sub-base fuel tanks
    • Integral & sub-base UL listed dual wall fuel tanks